How Much Ventilation Do I Need?

Ventilation products have differing capacities for moving air, so it's important to ensure that the unit you select has ample capacity for the application. HVI’s Certified airflow rating appears on the product or on the HVI label displayed on each unit, in the manufacturer’s literature describing the fan and in the HVI Certified Home Ventilating Products Directory available at www.hvi.org.

 

article continues below ↓

The following guidelines will help you to determine the fan capacity required for your application.

Bathrooms – intermittent ventilation

 

HVI recommends the following intermittent ventilation rates for bathrooms:

Bathroom size: Less than 100 sq. feet

 

Calculation formula: 1 CFM per sq. foot of floor area      

 

Ventilation rate required: A minimum of 50 CFM

 

Bathroom size: More than 100 sq. feet   

 

Add the CFM requirement for each fixture:  

 

 

Toilet          50 CFM
Shower       50 CFM
Bathtub      50 CFM
Jetted tub   100 CFM

• An enclosed toilet should have its own exhaust fan.
• Fans approved for installation in wet areas should be located over the shower or tub whenever possible.
• Bathroom doors need to have at least 3/4" clearance to the finished floor to allow proper entry of makeup air.
• A timer or other control that ensures ventilation continues for a minimum of 20 minutes after each use of the bathroom should be installed in each bathroom.
• For steam rooms, HVI recommends a separate fan located in the steam room that can be turned on after use to clear the heat and humidity.

Bathrooms – continuous ventilation

 

Continuous ventilation at a minimum rate of 20 CFM may be used in lieu of an intermittent 50 CFM exhaust fan.

Kitchen range hoods

Recommended kitchen range hood ventilation rates vary greatly depending on the type of cooking performed and the location of the range. Kitchen range hoods mounted above the range capture contaminants with their canopy shapes and exhaust them effectively with relatively low air volume. Downdraft kitchen exhausters require a higher volume and velocity of air to adequately capture contaminants. They are an alternative when canopy style hoods are not desired due to location of the cooking surface and kitchen aesthetics; however, their performance cannot equal that of hoods that capture the rising column of air above the cooking surface. When considering a downdraft kitchen exhauster, consult the range manufacturer’s recommendations.

Kitchen range hoods equipped with multiple speed settings allow low-level, quiet ventilation for light cooking with the ability for higher rates when needed.

Location of range            HVI recommended ventilation rate               Minimum ventilation rate

                                     per linear foot of range                                 per linear foot of range

 

Against a wall                100 CFM                                                     40 CFM
In an island                    150 CFM                                                     50 CFM

Width of hood against a wall       2.5 feet (30 in.)  3 feet (36 in.)         4 feet (48 in.)   
HVI recommended rate             250 CFM             300 CFM               400 CFM
Minimum                                 100 CFM             120 CFM                160 CFM

• For hoods located over islands multiply the rate by 1.5.
• For “professional-style” cooktops, HVI recommends following the cooktop manufacturer’s advice to determine ventilation requirements.
• Inflated performance ratings are common for range hoods that are not HVI-Certified. Selecting range hoods with HVI-Certified Performance Ratings will ensure that ventilation expectations and building code requirements are met.

Note: Nonducted, recirculation kitchen range hoods provide no actual ventilation. For optimum kitchen air quality, always use kitchen range hoods, kitchen fans or downdraft kitchen exhausters that vent directly outside the home.

Heat and energy recovery ventilators

For continuous indoor air quality ventilation, a heat or energy recovery ventilator (HRV or ERV) should provide 0.35 air changes per hour. This calculation must consider the complete occupied volume of the house.

This rate can be more easily calculated by allowing 5 CFM per 100 square feet of floor area.

Total area of home (sq. ft.)      Continuous ventilation rate
1,000 sq. feet                        50 CFM
2,000 sq. feet                        100 CFM
3,000 sq. feet                        150 CFM

In addition to this minimum, continuous ventilation rate, HRVs and ERVs often have additional capacity to provide higher ventilation rates to meet the occupants’ needs. Such needs could occur as a result of larger gatherings of people; smoking; a hobby or activity using paint, glues or other air-quality contaminants; or for any other reason that requires additional ventilation to improve the quality of indoor air.

Local codes may require different continuous ventilation rates – always check with your building officials to determine the specific requirements for your area.

Whole-house comfort ventilator

HVI recommends that a whole-house comfort ventilator have a minimum capacity to provide approximately one complete air change every two minutes within the occupied area. This flow rate will be great enough to create a perceptible “breeze” through the house. The required flow rate can be calculated by multiplying the gross square footage of the entire house (including unoccupied areas like closets) by 3. Be sure to include the “upstairs” area of multilevel homes. This formula assumes an eight-foot ceiling and takes into account typical unoccupied areas.

House area           Capacity in CFM
1,000 sq. feet      3,000 CFM
2,000 sq. feet      6,000 CFM
3,000 sq. feet      9,000 CFM

A smaller fan can effectively cool the mass of the house, relying on other fans such as “paddle-fans” to create the breeze needed to cool the people. This lower flow rate can be determined by multiplying the square footage by 0.4.

2,000 sq. feet      800 CFM
3,000 sq. feet      1,200 CFM

For proper cooling and efficient operation, any whole-house comfort ventilator requires adequate, unobstructed outlets in the attic through soffit vents, grilles or louvers.

To calculate the amount of attic exhaust area you will need, divide the fan’s capacity in CFM by 750.

Fan capacity      Exhaust area required
1,000 CFM         1.5 sq. feet
4,800 CFM         6.4 sq. feet

NOTE: Large fans can put the house under significant negative pressure. At least one window should be open before the fan is operated.

Powered attic ventilators – PAVs

 

Powered attic ventilators should provide at least 10 air changes per hour. Multiplying the total square footage of the attic by 0.7 will provide the rate required. For particularly dark or steep roofs, we recommend a slightly higher rating.

Attic area in sq. feet      CFM required      +15% for dark/steep roofs
1,000 sq. feet                   700 CFM              805 CFM
2,000 sq. feet                1,400 CFM            1,610 CFM
3,000 sq. feet                2,100 CFM            2,415 CFM

The air being exhausted must be replaced by outside air drawn through vents under the eaves in the soffit. To calculate the total minimum soffit vent intake area in square inches, divide the CFM of the PAV by 300 and multiply the result by 144.

CFM of PAV         Soffit vent in net sq. in.
805 CFM            386 net sq. inches
1,610 CFM          773 net sq. inches
2,415 CFM         1,160 net sq. inches

A minimum of one square foot of inlet area for every 300 CFM of HVI-Certified fan capacity is required for proper fan operation.
• Use only soffit vents as fresh-air intakes for powered attic ventilators.
• Do not use gable vents because it’s possible to draw rain and snow into the attic.

Static attic ventilation

In all seasons, the attic space is warmer than the outside air. This results in a constant upward air movement due to the buoyancy of warmer air. This characteristic of air may be used to help create a flow of air ventilating the attic. Placing exhaust vents in the roof, the gables or at the ridge of the roof and providing adequate air intake vents in the soffits best accomplishes this. HVI recommends vent selection and placement such that 60 percent of the vent net free area is provided by intake vents placed at the under-eave area and 40 percent of the vent net free area is provided by exhaust vents on the roof, at the ridge or high in the gable area.

To determine the static ventilator net free area (NFA) needed for your attic space, determine the area of the attic in square feet. Divide that area by 150 to determine the square feet of attic ventilation needed. Since manufacturers of static ventilation products rate their products in square inches of NFA, it will be necessary to multiply that value by 144 to determine the square inches required.

Attic area in sq. ft.      Ventilation area in sq. ft.         Net free area in sq. in.
1,000 sq. feet             6.67 sq. feet                           960 sq. inches
2,000 sq. feet             13.3 sq. feet                           1,920 sq. inches
3,000 sq. feet             20.0 sq. feet                           2,880 sq. inches

Static ventilation needs may be reduced if you have an uninterrupted ceiling vapor barrier installed with a rating of 0.1 perm or less. To calculate the ventilation required with such a vapor barrier, divide the square footage of the attic by 300 instead of 150.

Attic area in sq. ft.      Ventilation area in sq. ft.      Net free area in sq. in.
1,000 sq. feet              3.33 sq. feet                        480 sq. inches
2,000 sq. feet              6.67 sq. feet                        960 sq. inches
3,000 sq. feet              10.0 sq. feet                        1,440 sq. inches

Use these numbers to select, proportion and place static ventilation products.

The Healthy House Institute (HHI), a for-profit educational LLC, provides the information on HealthyHouseInstitute.com as a free service to the public. The intent is to disseminate accurate, verified and science-based information on creating healthy home environments.

 

While an effort is made to ensure the quality of the content and credibility of sources listed on this site, HHI provides no warranty - expressed or implied - and assumes no legal liability for the accuracy, completeness, or usefulness of any information, product or process disclosed on or in conjunction with the site. The views and opinions of the authors or originators expressed herein do not necessarily state or reflect those of HHI: its principals, executives, Board members, advisors or affiliates.

How Much Ventilation Do I Need?:  Created on December 14th, 2007.  Last Modified on December 8th, 2009

 

About The Home Ventilating Institute (HVI)

The Home Ventilating Institute (HVI)

The mission of the non-profit Home Ventilating Institute (HVI), Wauconda IL, is serving consumers and HVI members by advancing residential ventilation for healthier living. HVI does this by providing consumer information, participating in building code activities, and maintaining an active forum for the ventilation industry to meet and discuss common issues.  HVI is the leading name in residential ventilation product performance certification, providing the link between ventilation and healthy, energy efficient homes. Explore and sign up for The HVI Advantage, HVI's ventilation newsletter.

 

 

Information provided by The Healthy House Institute is designed to support, not to replace the relationship between patient/physician or other qualified healthcare provider.

Education Partners

 

 

Click to verify BBB accreditation and to see a BBB report.

Popular Topics: Air Cleaners & Air Purifiers | Allergies & Asthma | Energy Efficiency & Energy Savings | Healthy Homes | Green Building
Green Cleaning | Green Homes | Green Living | Green Remodeling | Indoor Air Quality | Water Filters | Water Quality

© 2006-2012 The Healthy House Institute, LLC.

 

About The Healthy House Institute | Contact HHI | HHI News & Media | Linking Resources | Advertising Info | Privacy Policy | Legal Disclaimer

 

HHI Info